Question 1: Does the rectifier system can make 110VAC input?
Answer :
Yes, it can be , but the output power only 50% of the capacity only
For example . 48VDC 30A 1440W rectifier system, If make 110vac input , the output power is 720W
Question2 : The 1U Rack Mount design rectifier system can install the LCD Display control module ?
Answer :
If install only one unit rectifier module , it can install the LCD Display control module
If install 2 units rectifier module , it can not install the LCD Display control module as the space limited
Question 3: what kind of specification of rectifier module have and what is the dimension ?
Answer :
Rectifier specification 48VDC /24VDC 10A 15A 20A 30A 50A
48VDC /24VDC 10A 15A 20A 30A, 1U Design
50A, 2U Design
Question 4 : does the distribution module specification can be customize or not ?
Answer :
Yes , it can customize according if the system have enough space to install
But the price would be change according
Question 5 : how many unit of rectifier module can install in different 1U 2U 3U rack mount
Answer :
Base of 48VDC /24VDC 10A 15A 20A 30 rectifier module
1U can install 2pcs rectifier module
2U can install 3pcs rectifier module
3U can install 5pcs rectifier module
Question 6 : the rectifier system YUCOO Manufacture can make SNMP or TCP/IP port and provide monitor protocol?
Answer :
No
At this moment , we only can supply RS485 Communication port and we can offer RS485 protocol
Buyer should be confirm for us before purchase , and the price should be different
The normal design with this port but did not open , it is no use
Question7 : If one of the rectifier module fail , does the rectifier system still can working ?
Answer :
Yes,
For example 48VDC30A Rectifier system use 2*15A Rectifier module , If one of 15A Module fail , the system can running at 15A output
Question 8 : what does the rectifier system efficiency?
Answer :
The efficiency more than 90% for all rectifier system YUCOO manufacture
Question 9: can you make a 48v 10A rectifier module and make it as one complete rectifier system?
Answer :
Yes
Question 10:What does the power supply system consist of ?
Answer:
Power system=Rectifier Module+ Monitor Module+DC Distribution Module+Rack mount
A Whole Rectifier System is composed of following item
No. QTY Item name Noted
1 1pc Rack Mount 1U/2U/3U**11U or cabinet option
2 1pc Monitor Module With LCD or without LCD Display option
3 *pc Rectifier Module 10A/20A/30A/50A option
*mean different QTY. for Example 2/3/4/5/6…pc.
4 1pc DC Distribution Stand alone DC Distribution or build in the system option
Question 11: For power system,what the input and output voltage you can customize?
Answer:
We can make the
input voltage:220VAC and 380VAC
Output voltage:24VDC and 48VDC
Question 12:What is the application of power system ?
Answer:
program-controlled switches
transmission equipment
data communications
mobile communications
railway communication
power communications
satellite communications
microwave communications
and other communications equipment.
Question13: Does your power system adopt N + 1 redundant modular design?
Answer:
Yes.
All power systems adopt current sharing N + 1 redundant modular design to ensure. safe and stable operation of the load.
Question 14:Can your power system add lighting protection?
Answer:
Yes
Please tell the sales to mark it.
Question 15:Can the rectifier system use in parallel?
Answer:
Yes.
If you have Two sets of 48V 30A, the you will finally get 48V 60A after make parallel operation.
Question 16:What is the connection type of transistor inside the rectifier system ?
Answer:
Full-Bridge type
Question 17 : Customer can purchase the rectifier module only?
Answer :
No
We sell the whole unit , but if the cooperation user with the rectifier broken , we can sell it
Question 18: what is the dimension of 1U/2U/3U Rectifier system ?
Answer :
Rack for rectifier System Dimension
1U 482.6*240*43.6 mm
2U 482.6*255*88mm
3U 482.6*253*130.5mm
Question 19 : what does the rectifier system apply for ?
Answer :
Small program-controlled switches
Access network
Transmission equipment
Mobile communication
Satellite communication earth station
Microwave communication power supply
Question 20: Can it accept different specification of rectifier module in one rectifier system>
Answer :
No
Once system accept one specification of rectifier module
Question 21 : what is the outstanding character with the rectifier module ?
Answer :
High temperature resistant
When temperature get to 55 ℃, it still with maximum power output and without temperature protection.
When temperature get to 55 ℃ ~ 65 ℃, the rate power output would reduce in automatic
It can keep 80% efficiency when the working environment under 65℃ and with 176~280 Vac Input
Question 22 : what is the main function of monitor module ?
Answer :
Item Remark
Remote monitoring of the host The host can conduct the remote message, remote sense and remote control.
Rectifier management by monitoring module To send controlling orders to or get data from the rectifier module via RS485.
Battery management To manage the low voltage, power down, equalizing/float charge, temperature compensation, capacity test of the battery.
Output management by monitoring module To inspect and control the system
LED indicator Signal indication
Sextuple dry contact output Dry contact setup
COM port signal RS485 TCP/IP
LCD Menu set up and modification
Dormancy function module monitoring module shut superfluous rectifier module, to save energy when the system with lower load
Question 23 : what is the specification of dc distribution module in rectifier system ?
Answer :
Including the BAT Port and LOAD Port
If there have special request for dc distribution module in rectifier system can customize
Question 24: Can you make the outdoor use rectifier system?
Answer:
Yes
We can customize for you, normally the YK rectifier system use for indoor machine room, and price will be more
Question 25: When the power supply system fails, how should we do?
Answer:
First, we should identify the reasons distinguish the load or power supply system, a host or a battery pack. Although the switching power supply system host has failed self-test function, but it does not point directly opposite, very convenient for replacement parts, but we have still to repair the fault point, still need to do a lot of analysis, detection work;
Also as part of the self-test fails, the fault display of the content may be wrong;
The host appears breakdown, insurance or burned off device fault, we must identify the reasons and to reboot after troubleshooting, otherwise the same spate of failure;
Even the best equipment there lifetime, there will be various types of failures, but maintenance work is done properly can extend the life and reduce the occurrence of failure, not because of high intelligence, maintenance and neglect of the maintenance work to be undertaken to prevent. It is an important guarantee for safe operation at any time.
Question 26: What is the methods of the rectifier system parallel operation use ?
Answer:
The first program (recommended):
1. First we sets a DC power source directly and machine capacity is also not limited, with only a monitor control rectifier operation, another monitor for the backup.
2. The monitor can be manually backup or automatic backup, switching power supply products because we have an indication of monitor monitor normal relay, may indicate a fault with the monitor manual backup automatic backup realize it is also more convenient.
3. The key point of this program is the exchange of loop-powered two systems must be independent circuit. Because the primary factor leading to the collapse of the entire system is AC-powered operation of the mine or overvoltage surges;
4. The use of two separate AC circuit power supply can greatly reduce the probability of the whole system crashes. DC converter can be solved and the machine after all flow, battery charging current limiting.
The second scheme: DC and machine monitor hot backup
The first scheme is basically the same, except that the monitor must SC200, SC200 use the monitor standby feature, due to the higher cost of using SC200, but it can be regarded as perfect and advanced machine. Line of Control between the two systems is also less and neat.
Third scenario: Diode and machine
Diode and machine is a traditional and more reliable solution, the old and new systems is not limited.
But disadvantages are:
1. There diode voltage drop is high energy consumption
2. Capacity is limited, we do 400A as highest one